Come back

А2XS(FL)H, 2XS(FL)H

Polyethylene-sheath single-core cables with aluminum or copper cores, XLPE-insulated, longitudinal or lateral sealing. As per IEC 62067, IEC 60332-1
А2XS(FL)H, 2XS(FL)H


copper or aluminum, multi-wire, compacted, and conforming to Class 2 as per IEC 60228. Conductors with cross-section 1000-2500mm2 are made of 5 sector-segments


made of electrically conductive XLPE


made of XLPE


made of electrically conductive XLPE


made of electrically conductive water-blocking tapes


copper wires layer covered by spiral copper screen

Notes:

- copper screen cross-section depends on short-circuit current magnitude and flow time and shall be specified at the time of order placing

- as per customer’s request, copper-wire screen may be equipped with fiber-optic temperature modules


made of electrically conductive water-blocking tapes


made of electrically conductive glass tapes


made of laminated aluminum polymeric tape tightly welded with outer sheath


made of flame-retardant halogen-free polymer compound

Cables are intended for electrical energy transmission and distribution in solidly grounded neutral systems with rated voltage 190/330 kV AC, 3ph, frequency 50 Hz, directly connected with overhead lines or without it, on paths with unlimited level difference. Cable is designed for fixed installation in electrical systems of public and industrial premises with corrosive gases exposure limits, as well as for open-air and in-ground installation.

Cable climatic version placement category 1 and 2 as per GOST 15150-69

Working temperature range: -60°С to +50°С

Cable lying down and installation without preheating shall be performed at temperature: not lower than -10° С

Min installation bending radius: up to 15 times of cable’s outer diameter

Max allowable forces developed during cable pulling along the path:

- for aluminum-core cables – 30 N/mm2

- for copper-core cables – 50 N/mm2

Allowable cable core heating temperatures:

- 90°С during normal operation of cable core

- 105°С at overload (max duration of overload operation shall be 100 h per year and no more than 1000 h per life cycle)

- 250°С when SC current flows in the core (max duration is 5 s)

- 350°С when SC current flows in the screen (max duration is 5 s)

Guarantee period is 3 years (from the date of cable commissioning)