(A)YBY

PVC compound insulated armored power cables with copper or aluminum cores, with PVC compound sheath

PVC compound insulated armored power cables with copper or aluminum cores, with low-flammable PVC compound sheath


copper or aluminum, single- or multi-wire, round and sectoral shape, conforming to Class 1 or 2 as per GOST 22483


made of PVC compound

Insulated cores of multicore cables have distinguishing color

Neutral cores insulation is blue

Grounding core insulation is two-color (yellow and green)


insulated cores of two-, three-, four- and five-core cables are twisted with each other; cores of two-, three- and five-core cables are of the same cross-section, in four-core cables all the cores are of the same cross-section or one core (grounding or neutral) has smaller cross-section


PVC compound for cables, low-flammable PVC compound


two steel zinc plated bands


PVC compound & low-flammable PVC compound

Cables are intended for electrical energy transmission and distribution in stationary installations with rated voltage 0.66; 1 and 3kV AC, 50 Hz, incl. overhead installation providing that solar radiation protection is ensured. (A)YBY for single cabling in cable trays and industrial premises. For bunched wiring passive fire protection means implementation is mandatory. In case of single wiring cables are flame-retardant, for bunched wiring in cable trays, outdoor (open) electrical systems (cable bridges, cable walkways). In case of bunched wiring cables are flame-retardant.

Operating temperature range from -50°С to +50°С

Ambient relative humidity at +35°С up to 98%

Cable lying down and installation without preheating shall be performed at temperature not lower than -15°С

Min installation bending radius:

- for single-core cables – 10 times of cable OD

- for multi-core cables – up to 7.5 times of cable OD

Max allowable forces developed during cable pulling along the path:

- for aluminum-core cables – 30 N/mm2

- for copper-core cables – 50 N/mm2

Continuous temperature of cable conductor heating during operation is +70°С

Cable conductor allowable heating during overload is no more than +90°С

Limiting cable conductor temperature at short-circuit (max duration is 5 s) is +160°С

Guarantee service life is 5 years (since cable commissioning)

Service life is at least 30 years